Published 12 June 2026 22 min read · the essentials in 2 min IWI · Hygrothermal LCI 114A · RCI 56A · SIA 180 Updated June 2026

Insulating from the inside without creating defects

A protected façade, a co-ownership that cannot decide, architectural expression to preserve: when external insulation is not possible, internal wall insulation (IWI) remains the way forward. It is the most demanding insulation technique to design — not because it is complicated to install, but because it changes the physics of the wall. This guide explains when IWI is justified, what happens inside the wall, which systems to choose, and where defects arise.

In this guide

When IWI is required — and when it should not be used

One reminder, in a sentence, before the subject itself: external wall insulation remains the reference solution whenever it is possible, and in Geneva the building envelope limits are no longer an argument against it — LCI art. 114A provides that the thickness of external insulation counts neither in the calculation of the building envelopeLCI art. 114A para. 3: the thickness of external insulation on an existing building counts neither in the building profile nor in the distances to property boundaries or between buildings.République et canton de Genève — rsGE L 5 05 — Loi sur les constructions et les installations diverses (LCI), art. 114A — Isolation périphérique de constructions existantesaccessed 2026-08-29 nor in that of the distances to boundaries (para. 3). That lever is covered in the thermal bridges dossier.

IWI is therefore not a matter of convenience: it is the option left when the façade cannot change. Four situations, and only those:

Heritage
Protected or high-value façade
A protected zone, mouldings, dressed stone or exposed molasse sandstone: covering the façade is rejected at the preliminary review stage.
Co-ownership
Collective decision not achievable
The façade is a common part: going outside requires a decision by the condominium association and collective financing. A single owner can insulate their unit from the inside.
Partial intervention
An apartment, a room, a unit
A single dwelling, an attic conversion, a ground-floor commercial space: scaffolding is not justified.
Complement
Specific walls within a wider project
Party walls that have become external, walls onto a narrow courtyard, gable walls at the boundary: unreachable from outside.
Insulating from the inside means moving the cold into the wall. The question is not whether water vapour will get in — but how it will get back out.
What about French-speaking Switzerland and neighbouring France? The logic is the same everywhere. In the French-speaking cantons, heritage inventories play the role of Geneva's protected zones. In neighbouring France, the Architectes des Bâtiments de France often require IWI within protected perimeters; MaPrimeRénov' supports wall insulation mainly through the "rénovation d'ampleur" pathwayFrance Rénov': in the 'rénovation d'ampleur' pathway, support by a Mon Accompagnateur Rénov' is compulsory and at least two insulation measures (walls among them) are required.France Rénov' — Anah / Ministère de la Transition écologique — MaPrimeRénov' pour une rénovation d'ampleur2026 · accessed 2026-08-20 — a supervised package of works tied to a gain in DPE classes, as against the parcours par geste.

Wall physics: what IWI changes

An uninsulated old wall is crossed by a constant flow of heat, and this waste has a useful side effect: the wall stays warm and dry. IWI interrupts that flow — that is the point — and simultaneously places the entire masonry on the cold side: a wall that used to sit at 12–15 °C behind the plaster drops close to the outdoor temperature behind the insulation.

The dew point migrates into the wall

The water vapour produced indoors diffuses through the materials, from warm to cold. As long as the temperature inside the wall stays above the dew point, it remains gaseous; but behind an IWI system the temperature drops sharply at the interface between the insulation and the wall, and the vapour that reaches it condenses. This is interstitial condensation — invisible, because it occurs behind the lining.

All of it develops silently: dampening of the masonry, mould on the hidden face of the lining, corrosion of the fixings, frost damage to porous materials — and, in buildings with timber floors, rot in the joist ends.

≈ 12 g/m³
of water vapour in air at 20 °C / 70 % RH — it starts to condense as soon as the air meets a surface at ~14 °CEnergie+, 'Tableau de valeurs': at 20 °C, ρvs = 17.3 g/m³ and xs = 14.7 g/kg. The 12 g/m³ at 70 % RH and the 14 °C dew point are derived from it — they are not published as such.Energie+ (Architecture et Climat, UCLouvain — Service public de Wallonie) — Grandeurs hygrométriques — « Tableau de valeurs » (pvs, ρvs, xs par température)2007 · accessed 2026-09-04
−10 to −15 °C
difference in the internal wall surface temperature of the old wall, before/after IWI, in mid-winter
SIA 180:2014
the Swiss standard on hygrothermal protection: any modified wallSIA 180:2014 'Thermal protection, moisture protection and indoor climate in buildings'; to be read with corrigenda C1:2015 and C2:2020 and guideline SIA 4001:2022.SIA — Société suisse des ingénieurs et des architectes — SIA 4001:2022 — Lignes directrices relatives à la norme SIA 180:2014 (Protection thermique, protection contre l'humidité et climat intérieur dans les bâtiments)2022 · accessed 2026-08-20 must be checked against condensation
2 directions
the wall must be able to dry — outward (driving rain) and, if possible, inward (capillarity)

Glaser for pre-sizing, dynamic simulation as the ruleWTA 6-4 (10.2016/D), Kurzfassung: for interior insulation, moisture protection is verified by coupled heat-and-moisture simulation to WTA 6-1 and 6-2, criteria in 6-5. Glaser is not mentioned.WTA — Wissenschaftlich-Technische Arbeitsgemeinschaft für Bauwerkserhaltung und Denkmalpflege — Merkblatt WTA 6-4 — Innendämmung nach WTA I: Planungsleitfaden (10.2016/D), Kurzfassung2016-10 · accessed 2026-09-04

The Glaser calculation (steady-state diffusion method, EN ISO 13788)ISO 13788:2012 provides simplified methods (monthly balance, steady state) for interstitial condensation and critical surface humidity. Confirmed in 2023.ISO — ISO 13788:2012 — Hygrothermal performance of building components and building elements — Internal surface temperature to avoid critical surface humidity and interstitial condensation — Calculation methods2012 · accessed 2026-08-20 is a pre-sizing tool, never a design justification: it ignores the two phenomena that are decisive for old walls, the driving rain absorbed by the façade and the capillary transport of liquid water. In internal wall insulation, dynamic hygrothermal simulation (such as WUFI, per EN 15026) is the rule and not the exceptionEN 15026:2007 sets the minimum criteria for transient coupled heat-and-moisture transfer software; Fraunhofer IBP states that WUFI meets them (deviation ≤ 2.5 %). The page carries no date.Fraunhofer IBP — WUFI — Benchmark test of EN 15026 (EN 15026:2007) — page non datéeaccessed 2026-09-04: WTA leaflet 6-4 prescribes verification by coupled heat and moisture transport calculation (WTA 6-1, 6-2 and 6-5), hour by hour and over several years. A few days' study, against a lining that has to be removed.

The two risk criteria to demand from the study A hygrothermal study is not judged on a reassuring conclusion but on two quantified criteria. Mould: the surface relative humidity, indoors and at every interface within the wall, must stay below 80 % as a monthly meanISO 13788:2012 § 5.1: 'There is a risk of mould growth when monthly mean surface relative humidities are above a critical relative humidity, φsi,cr, which should be taken as 0,8'.ISO — ISO 13788:2012 — Internal surface temperature to avoid critical surface humidity and interstitial condensation (extrait officiel, § 5.1)2012 · accessed 2026-08-20 — this is the φsi,cr = 0,8 criterion of EN ISO 13788, refined by the Sedlbauer isopleths, which combine humidity, temperature and exposure time. Timber decay: the moisture content of embedded joist ends must remain durably below 20 % by massAQC sheet 'Attaques des bois par les agents biologiques': decay results from 'le maintien d'une humidité relative supérieure à 20 %' in the timber — the sheet's wording is ambiguous.AQC — Agence Qualité Construction — Fiche pathologie bâtiment — Les attaques des bois par les agents biologiques2013 · accessed 2026-09-04, the threshold above which wood-destroying fungi develop. Both figures must appear in black and white in the report, backed by multi-year curves.
NRG positive rule of caution No IWI on a wall whose moisture condition is unknown. Rising damp, a cracked façade, exterior render not watertight against driving rain: these defects are diagnosed and treated before the insulation is installed. IWI on a damp wall systematically makes things worse — it removes drying to the inside and cools the wall.

Common errors and documented defects

IWI failures tend to look alike: they rarely stem from the material, almost always from a design error or an execution defect at a critical point. The typical cases below recur throughout the technical literature and failure investigations.

Error Defect observed Prevention
IWI on a damp wall (rising damp, untreated driving rain) Increasing moisture in the masonry, efflorescence, render delamination, widespread mould behind the lining Prior moisture diagnosis; treat the cause of the dampness before insulating
Vapour barrier punctured or not connected (outlets, conduits, joints, partition bases) Condensation concentrated at the leaks, localised mould stains, odours — often discovered years later A drawn-up airtightness plan, a service cavity, inspection before closing up
Excess insulation thickness ("while we're at it, let's put 18 cm") Wall too cold: interstitial condensation, frost damage to the masonry, deterioration of soft stone Thickness set by the hygrothermal study, not by U-value ambition
Untreated reveals and cross walls Mould on window jambs and at ceiling/façade corners — the cold point has moved, not been eliminated Systematic insulation returns, thin insulation of the jambs (RCI art. 56A)
Water pipes left in the cold wall Frozen pipes in the first hard winter, water damage in the new lining Move the pipework to the warm side during the works
Ventilation overlooked after the dwelling is sealed up Rising indoor humidity, condensation on residual cold points, degraded air quality A ventilation concept at minimum, or balanced mechanical ventilation with heat recovery, in every IWI project
Verification limited to a summary Glaser check on an exposed old wall Wall validated on paper, damaged in reality — driving rain and capillarity were not in the calculation Dynamic simulation (WUFI, EN 15026) for old walls, embedded timber, exposed façades

The common thread among these defects: they are invisible at handover and appear in the second or third winter. Hence the importance of design — the contractor cannot fix a wall that was poorly conceived.

IWI systems: four families, two philosophies

Two opposing philosophies: blocking the vapour before it reaches the cold wall (vapour barrier), or letting it in and redistributing it so it gets back out without damage (capillary-active materials). A capillary-active material takes up liquid water, spreads it through its mass and gives it back to the indoor air as that air dries out: it does not merely let vapour through. Two figures make the four families below readable.

The two figures that decide: µ and sd µ is the water vapour diffusion resistance factor (µ = 1 for air); sd = µ × thickness, in metres of equivalent air layer. Conventional vapour barrier: sd above 15 m. Humidity-variable vapour retarderPassipedia (PHI), interior insulation: 'a minimum value of more than 15 m should be complied with for the effective water vapour diffusion-equivalent thickness' of the vapour barrier.Passipedia — Passive House Institute — Thermal protection using interior insulation2019 · accessed 2026-08-20: around 0,25 m in summerpro clima INTELLO product data: humidity-variable sd from 0.25 m (summer, wall drying out) to over 25 m (winter, wall protected). Typical range for humidity-variable vapour retarders.Eurabo (distributeur — donnée produit pro clima) — pro clima INTELLO — frein-vapeur hygrovariable, valeur Sd 0,25 à >25 m2024 · accessed 2026-08-20 — when the wall must dry inwards — rising above 10 m in winter. Capillary-active materials: µ ≈ 2–3 for calcium silicate and mineral boardsMultipor technical data sheet: µ = 2 (λD 0.042) to µ = 3 (λD 0.045/0.047). Calsitherm Klimaplatte: µ = 3 per European approval, 3.6 measured. Materials effectively open to diffusion.Xella / Multipor (fabricant — donnée produit) — Multipor Mineraldämmplatte — Technisches Datenblatt2023 · accessed 2026-08-20, hence open to diffusion, which is precisely the point. Wood fibre for IWI: µ = 5.STEICO internal technical data sheet (wood fibre for IWI): µ = 5, λD = 0.038 W/(m·K), density 160 kg/m³, bonded over ≥ 80 % of the surface.STEICO SE (fabricant — donnée produit) — Fiche technique STEICO internal — isolant support d'enduit intérieur2021 · accessed 2026-08-20 A system is only coherent if the sd matches the drying capacity of the wall — the hygrothermal study establishes that, not the product data sheet.
Mineral wool + vapour barrier
λ ≈ 0,032–0,040 W/(m·K)Passipedia (PHI) uses conductivity classes 035 to 040 for interior insulation, i.e. λ = 0.035–0.040 W/(m·K). The 0.032 of high-performance wools does not appear in this source.Passipedia — Passive House Institute — Thermal protection using interior insulation2019 · accessed 2026-08-20
Framing + plasterboard lining · philosophy: block the vapour
When — low-risk walls, a contractor experienced with vapour sealing. Why not — its reliability rests entirely on the absolute continuity of the vapour barrier; punctured, it concentrates vapour on a few points of the cold wall. How much — the most economical system on the market.
Bonded composite panels
λ ≈ 0,022–0,040 W/(m·K)Manufacturer data, sheet footer dated 211025: PIR λD = 0.022 W/(m·K), µ = 50–100; composite panels with laminated mineral wool reach 0.035–0.040 W/(m·K). Hence the 0.022–0.040 range.Recticel Insulation (fabricant — donnée produit) — Fiche technique IP PIR 022 (pied de page 211025)2021-10-25 · accessed 2026-09-04
Insulation + plasterboard · low thickness · built-in vapour retarder
When — where the loss of floor area must be minimal and the site short. Why not — the joints between panels and the air gaps behind the adhesive dabs short-circuit the vapour retarder. How much — a step above mineral wool.
Capillary-active — calcium silicate, aerated concrete
λ ≈ 0,042–0,070 W/(m·K)Manufacturer data: Calsitherm Klimaplatte λ = 0.062 W/(m·K) (measured 0.059), µ = 3; Multipor λD = 0.042–0.047 W/(m·K), µ = 2–3. The stated range is correct.Calsitherm Silikatbaustoffe GmbH (fabricant — donnée produit) — CALSITHERM Klimaplatte — Technische Hinweise 20182018 · accessed 2026-08-20
Full-surface bonding + mineral render · philosophy: manage moisture
When — old walls, heritage, embedded timber: the reference system, without a vapour barrier, tolerant of defects and the unexpected. Why not — less insulating per centimetre. Full-surface bonding (no air gap) is essential for it to work.Calsitherm: boards must be bonded 'hohlraumfrei und vollflächig' (void-free, full-surface); dab or partial bonding is not system-compliant and causes uncontrolled condensation behind the insulation.Calsitherm Silikatbaustoffe GmbH (fabricant — prescription de mise en œuvre) — CALSITHERM Klimaplatte — Technische Hinweise 20182018 · accessed 2026-08-20 How much — the most expensive of the four.
Bio-based — wood fibre, hemp
λ ≈ 0,038–0,045 W/(m·K)Manufacturer data: STEICO internal (wood fibre for IWI) λD = 0.038 W/(m·K), µ = 5, density 160 kg/m³, bonded over the full surface (≥ 80 % adhesive coverage).STEICO SE (fabricant — donnée produit) — Fiche technique STEICO internal — isolant support d'enduit intérieur2021 · accessed 2026-08-20
Humidity-variable vapour retarder · good hygric behaviour
When — old masonry, and projects aiming at low-embodied-carbon materials (LCI art. 117)LCI art. 117: 'Any construction or significant renovation must be designed and built with materials that minimise its carbon footprint'; art. 118 sets the calculation method.Office cantonal de l'architecture / EPIQR+ — Articles 117-118 LCI — présentation de Francesco Della Casa, architecte cantonal, République et canton de Genève2024-03-14 · accessed 2026-08-20. Why not — the humidity-variable vapour retarder has to be laid without interruption, like any control plane. How much — between the composite and the capillary-active system.

How thick? Less than you think

In IWI, more insulation is not better: each additional centimetre cools the wall further. Practice converges on 6 to 10 cm, giving a renovated wall around U ≈ 0,25–0,40 W/(m²K). The SIA 380/1:2016 element-by-element limit value is 0,25 W/(m²K) for a wall undergoing conversion (0,17 W/(m²K) for a new element)EN-NE102, April 2023 edition (based on SIA 380/1:2016), table 2 p. 9: opaque element against outside air, U ≤ 0.17 W/(m²K) for new build and 0.25 W/(m²K) for conversion.République et canton de Neuchâtel — Service de l'énergie et de l'environnement — Aide à l'application EN-NE102 « Isolation thermique des bâtiments », édition avril 2023 (base SIA 380/1:2016)2023-04 · accessed 2026-09-04. RCI art. 56 (the implementing regulation of the LCI, rsGE L 5 05.01)RCI (rsGE L 5 05.01) art. 56: 'The thermal quality of the building envelope must, unless a particular case applies, comply with the SIA 380/1 standard in force.'République et canton de Genève — SILGeneve — Règlement d'application de la loi sur les constructions et les installations diverses (RCI), L 5 05.01, art. 561978-12-27 · accessed 2026-08-20 requires SIA 380/1 compliance "unless a particular case applies", and the justification can be based on the building's overall performance. The hygrothermal study sets the maximum admissible thickness — not the insulation catalogue.

IWI within a label strategy A wall with IWI does not rule out an HPE renovation target — haute performance énergétique, a statutory Geneva standard rather than a label (heating demand ≤ SIA 380/1 limit values increased by 50 %, REn art. 12BREn (L 2 30.01) art. 12B, HPE renovation, variant a): MoPEC 2014 weighted energy demand limits increased by 70 % and SIA 380/1 heating demand increased by 50 %.République et canton de Genève — SILGeneve — Règlement d'application de la loi sur l'énergie (REn), L 2 30.01, art. 12B2010-09-01 · accessed 2026-08-20), a Minergie® Rénovation certification, or an EnerPHit component-based approach — which explicitly provides for internal insulation with adapted requirementsUnconfirmed claim: the PHI document 'Criteria for the Passive House, EnerPHit and PHI Low Energy Building Standard' could not be opened. To be sourced or removed before publication.Source to be established — unverified figure.

Critical points: cross walls, window reveals, pipework, air — and the Geneva stock

With EWI, the insulation wraps the building continuously. With IWI, the insulation plane is interrupted by the building's own structure: every cross wall, every slab, every window reveal crosses through the insulation. This is where heat flows — and defects — concentrate.

Critical
Cross walls and slabs: structural thermal bridges
Cross walls and slabs remain connected to the cold wall: at these junctions the surface temperature drops, and mould appears on ceilings and in corners. Treatment: insulation returns (Flankendämmung) of the order of 40 cm on the cross walls and slabsPassipedia (PHI): 'flanking insulation along the interior wall (ca. 40 cm)', with ≥ 20 mm at the window reveal and an insulation wedge on the underside of the slab.Passipedia — Passive House Institute — Thermal protection using interior insulation2019 · accessed 2026-08-20, their length confirmed by the thermal bridge calculation per EN ISO 10211.
Critical
Window reveals — RCI art. 56A
Jambs, lintels and roller shutter boxes are the coldest points of the insulated wall. In existing buildings, the U-value of the whole reveal — glazing, frame and roller shutter box — must be brought to 3,0 W/(m²K) or belowRCI art. 56A para. 2: reveals to be upgraded from U ≥ 3.0 W/(m²K). Para. 5, protected buildings: let. a, b and d require glazing U ≤ 1.0; let. c, a second external window, is single-glazed.République et canton de Genève — SILGeneve — Règlement d'application de la loi sur les constructions et les installations diverses (RCI), L 5 05.01, art. 56A1978-12-27 · accessed 2026-09-04 (RCI art. 56A); in protected zones, derogating variants are admitted on justification, each with a U-value ≤ 1,0 W/(m²K). In practice: insulate the jambs even with 2–3 cm of a high-performance panel, and treat the joinery-to-insulation junction as a continuous plane.
Caution
Pipework in the now-cold wall
A water pipe embedded in a wall insulated from the inside ends up on the cold side: it will freeze. Move water services to the warm side. Electrical boxes penetrate the vapour barrier: sealed boxes or a service cavity in front of the airtightness plane.
Caution
Airtightness: no convection behind the insulation
If indoor air circulates behind the insulation (an unsealed air gap, a lining not sealed at floor and ceiling), it carries its vapour straight onto the cold wall — convection transports far more moisture than diffusionpro clima (DIN 4108-type test): 0.5 g of water/m² per winter day by diffusion through an sd = 30 m vapour retarder, versus 800 g per metre of a 1 mm gap by convection — a factor of 1600.pro clima Suisse — Éviter les dégâts au bâtiment2020 · accessed 2026-08-20. The airtightness plane must be continuous and connected to the floor, ceiling and joinery.
Joist ends: the detail that decides the system In buildings with timber floors, the joists are embedded in the façade walls — at every level, on every façade, dozens of times in a late-19th-century building. After IWI, these embedments sit in the cold, potentially damp zone of the wall: rot in the joist ends is the most severe defect documented in internal insulationAQC sheet 'Attaques des bois par les agents biologiques': decay results from 'le maintien d'une humidité relative supérieure à 20 %' in the timber — the sheet's wording is ambiguous.AQC — Agence Qualité Construction — Fiche pathologie bâtiment — Les attaques des bois par les agents biologiques2013 · accessed 2026-09-04. A dynamic hygrothermal check is mandatory — demonstrating that the moisture content of the embedded ends stays durably below 20 % by mass —, a capillary-active system is strongly recommended, and in some cases moisture monitoring of the embedments is warranted.

The Geneva stock: late-19th-century buildings

The Geneva stock affected by IWI largely belongs to the urban ring of the late 19th and early 20th centuries: massive masonry — rubble stone, brick, dressed stone and molasse sandstone —, moulded façades, timber floors. These buildings often fall within protected zones or ensembles under the LCI: review by the CMNS (Commission des monuments, de la nature et des sites), and covering the façades is generally excluded.

Two Geneva particularities to factor in from the study stage

Molasse sandstone does not tolerate damp. A soft, porous stone present in many Geneva plinths and surrounds, it is sensitive to frost and wetting cycles, and a poorly designed IWI accelerates its deterioration — on the street side, precisely where it is visible and protected. The study must model the actual stone, not a generic wall.

The legal framework offers some latitude. RCI art. 56A provides for exemptions for protected buildings, on justification, and envelope compliance is assessed "unless a particular case applies" (RCI art. 56). A moderate, well-designed IWI, combined with high-performance windows, an insulated roof and controlled ventilation, makes for a defensible case before both the OCEN — the cantonal energy office — and the CMNS.

IDC: the lever that makes IWI relevant today

The IDC — indice de dépense de chaleur — is the actual heating and hot water consumption read off the building's meters and declared to the canton every year. It is not a theoretical calculation, and the instrument is cantonal. Three thresholds, and only those, decide:

What it triggersThresholdPeriod
Mandatory auditIDC threshold of 125 kWh/m²·an (450 MJ/m²·an) that triggers a mandatory auditREn art. 14: exceeding an IDC of 125 kWh/m²·an (450 MJ/m²·an) requires an audit and improvement measures within 12 months.République et canton de Genève — SILGeneve — Règlement d'application de la loi sur l'énergie (REn), L 2 30.01, art. 142010-09-01 · accessed 2026-08-20at all times
Mandatory works
significant exceedance, REn art. 14
222 kWh/m²·an (800 MJ/m²·an)until 31.12.2026
180 kWh/m²·an (650 MJ/m²·an) from 2027 to 2030REn art. 14: significant IDC exceedance at 222 kWh/m²·an (800 MJ) until 31.12.2026, 180 kWh/m²·an (650 MJ) from 2027 to 2030, then 153 kWh/m²·an (550 MJ) from 2031.République et canton de Genève — SILGeneve — Règlement d'application de la loi sur l'énergie (REn), L 2 30.01, art. 142010-09-01 · accessed 2026-08-202027–2030
153 kWh/m²·an (550 MJ/m²·an)from 2031

When the façade cannot change, IWI is one of the levers to consider for bringing the index down, alongside the roof, windows and systems. See the guide Renovating in Geneva: IDC, standards and strategy →

The cantonal architectural surveys of Vaud, Neuchâtel and Fribourg produce the same constraints on historic centres; in neighbouring France, ABF perimeters lead to the same trade-off.

What clients ask

How much living space will I lose?

Allow 8 to 14 cm of total thickness (insulation + lining) on each façade wall, depending on the system. For a 4 × 5 m room with two external walls, that amounts to roughly 0,8 to 1,2 m². It is real, but should be weighed against the comfort gained: the inner wall surface goes from roughly 14–16 °C to 18–19 °C depending on how hard the winter isISO 6946 calculation (Rsi = 0.13 m²K/W): Tsi = Ti − U·Rsi·(Ti−Te). Wall U = 1.8 at 20/0 °C → 15.3 °C; at 20/−5 °C → 14.2 °C; after IWI U = 0.30 → 19.2 °C.ISO — ISO 6946:2017 — Building components and building elements — Thermal resistance and thermal transmittance — Calculation methods2017-06 · accessed 2026-08-20, which removes the cold-wall sensation and often allows the thermostat setpoint to be lowered by a degree.

Can I insulate my apartment alone, without a decision from the co-ownership?

In principle, yes: IWI is carried out within your unit, without touching the common parts — this is one of its advantages. Two caveats: check the condominium regulations (some work that indirectly affects the structure or the façades requires notice or approval), and above all have the wall checked by a hygrothermal study, since a moisture defect in the wall would affect the whole building, not just your unit. In a building subject to authorisation (protected zone, listed building), check with the cantonal office before starting work.

How much does IWI cost?

NRG positive estimate as of June 2026 — no public Swiss cost database covers IWI specifically — supply and installation, finishes included: CHF 150 to 250/m²Internal NRG positive estimate (June 2026): no public Swiss cost database (CRB, KBOB, SIA Bulletin) covers internal insulation specifically. Order of magnitude, not contractual.Source to be established — unverified figure of wall for a mineral wool lining with vapour barrier, CHF 200 to 300/m² for composite panels, CHF 250 to 450/m² for a capillary-active system such as calcium silicate with mineral render. On top of this come the insulation returns, treatment of the reveals and any relocation of pipework — often 20 to 30 % of the budget, and the part that makes the difference between a healthy wall and a failure. The hygrothermal study represents a modest fraction of the total.

Is a hygrothermal study really necessary for a few centimetres of insulation?

Yes — and all the more so when the wall is old. It is precisely the thin layer that needs to be justified: the right IWI is one whose thickness, material and details have been checked for your wall specifically, with its orientation, its exposure to rain and its floors. SIA 180:2014 requires hygrothermal verification of modified walls; for old walls and embedded timber, a Glaser calculation is not enough and a dynamic simulation is required. A few days of study against years of hidden defects: the trade-off is easily made.

Is IWI alone enough to bring my IDC below Geneva's thresholds?

Rarely on its own. Walls account for a significant share of heat loss, but the roof, windows, ventilation and heat generation together weigh more. IWI makes sense within an overall strategy: it is the audit (mandatory above an IDC of 125 kWh/m²·an / 450 MJ/m²·an) that prioritises the measures and their timeline. A renovation planned holistically — even if carried out in stages — is better than a stand-alone IWI decided when repainting.

What to take away, and in what order to act

  1. Establish the moisture state of the wall first. Rising damp, a cracked façade, render that is not rain-tight: treat the cause before any insulation goes on.
  2. Commission the dynamic hygrothermal study. It, and not the insulation catalogue, sets the maximum admissible thickness and the type of system.
  3. Decide the philosophy before the product. Blocking the vapour requires a perfectly continuous vapour barrier; managing it requires a fully bonded capillary-active build-up.
  4. Deal with the singular points in the same contract. Insulation returns on cross walls and slabs, insulated reveals, water pipes moved to the warm side, continuous airtightness.
  5. Plan the ventilation. A dwelling sealed without a ventilation concept simply moves the moisture onto the remaining cold spots.

GenevaProtected zones and ensembles, CMNS opinion, RCI art. 56A for reveals with derogations on justification. Above an IDC of 125 kWh/m²·an, the audit is mandatory (REn art. 14).

SwitzerlandThe architectural inventories of Vaud, Neuchâtel and Fribourg create the same constraints in the old town centres. SIA 180:2014 requires every modified wall to be verified.

Neighbouring FranceWithin ABF perimeters, internal insulation is often the only option. MaPrimeRénov' supports it through the supervised "rénovation d'ampleur" route — not through the parcours par geste.

Sources and references (31)

Every figure and every claim in this dossier links back to its source. Hover or tap a footnote marker to see it.

  1. République et canton de Genève — rsGE L 5 05 — Loi sur les constructions et les installations diverses (LCI), art. 114A — Isolation périphérique de constructions existantes (accessed 2026-08-29)
    LCI art. 114A para. 3: the thickness of external insulation on an existing building counts neither in the building profile nor in the distances to property boundaries or between buildings.
  2. France Rénov' — Anah / Ministère de la Transition écologique — MaPrimeRénov' pour une rénovation d'ampleur (2026 · accessed 2026-08-20)
    France Rénov': in the 'rénovation d'ampleur' pathway, support by a Mon Accompagnateur Rénov' is compulsory and at least two insulation measures (walls among them) are required.
  3. Energie+ (Architecture et Climat, UCLouvain — Service public de Wallonie) — Grandeurs hygrométriques — « Tableau de valeurs » (pvs, ρvs, xs par température) (2007 · accessed 2026-09-04)
    Energie+, 'Tableau de valeurs': at 20 °C, ρvs = 17.3 g/m³ and xs = 14.7 g/kg. The 12 g/m³ at 70 % RH and the 14 °C dew point are derived from it — they are not published as such.
  4. SIA — Société suisse des ingénieurs et des architectes — SIA 4001:2022 — Lignes directrices relatives à la norme SIA 180:2014 (Protection thermique, protection contre l'humidité et climat intérieur dans les bâtiments) (2022 · accessed 2026-08-20)
    SIA 180:2014 'Thermal protection, moisture protection and indoor climate in buildings'; to be read with corrigenda C1:2015 and C2:2020 and guideline SIA 4001:2022.
  5. WTA — Wissenschaftlich-Technische Arbeitsgemeinschaft für Bauwerkserhaltung und Denkmalpflege — Merkblatt WTA 6-4 — Innendämmung nach WTA I: Planungsleitfaden (10.2016/D), Kurzfassung (2016-10 · accessed 2026-09-04)
    WTA 6-4 (10.2016/D), Kurzfassung: for interior insulation, moisture protection is verified by coupled heat-and-moisture simulation to WTA 6-1 and 6-2, criteria in 6-5. Glaser is not mentioned.
  6. ISO — ISO 13788:2012 — Hygrothermal performance of building components and building elements — Internal surface temperature to avoid critical surface humidity and interstitial condensation — Calculation methods (2012 · accessed 2026-08-20)
    ISO 13788:2012 provides simplified methods (monthly balance, steady state) for interstitial condensation and critical surface humidity. Confirmed in 2023.
  7. Fraunhofer IBP — WUFI — Benchmark test of EN 15026 (EN 15026:2007) — page non datée (accessed 2026-09-04)
    EN 15026:2007 sets the minimum criteria for transient coupled heat-and-moisture transfer software; Fraunhofer IBP states that WUFI meets them (deviation ≤ 2.5 %). The page carries no date.
  8. ISO — ISO 13788:2012 — Internal surface temperature to avoid critical surface humidity and interstitial condensation (extrait officiel, § 5.1) (2012 · accessed 2026-08-20)
    ISO 13788:2012 § 5.1: 'There is a risk of mould growth when monthly mean surface relative humidities are above a critical relative humidity, φsi,cr, which should be taken as 0,8'.
  9. AQC — Agence Qualité Construction — Fiche pathologie bâtiment — Les attaques des bois par les agents biologiques (2013 · accessed 2026-09-04)
    AQC sheet 'Attaques des bois par les agents biologiques': decay results from 'le maintien d'une humidité relative supérieure à 20 %' in the timber — the sheet's wording is ambiguous.
  10. Passipedia — Passive House Institute — Thermal protection using interior insulation (2019 · accessed 2026-08-20)
    Passipedia (PHI), interior insulation: 'a minimum value of more than 15 m should be complied with for the effective water vapour diffusion-equivalent thickness' of the vapour barrier.
  11. Eurabo (distributeur — donnée produit pro clima) — pro clima INTELLO — frein-vapeur hygrovariable, valeur Sd 0,25 à >25 m (2024 · accessed 2026-08-20)
    pro clima INTELLO product data: humidity-variable sd from 0.25 m (summer, wall drying out) to over 25 m (winter, wall protected). Typical range for humidity-variable vapour retarders.
  12. Xella / Multipor (fabricant — donnée produit) — Multipor Mineraldämmplatte — Technisches Datenblatt (2023 · accessed 2026-08-20)
    Multipor technical data sheet: µ = 2 (λD 0.042) to µ = 3 (λD 0.045/0.047). Calsitherm Klimaplatte: µ = 3 per European approval, 3.6 measured. Materials effectively open to diffusion.
  13. STEICO SE (fabricant — donnée produit) — Fiche technique STEICO internal — isolant support d'enduit intérieur (2021 · accessed 2026-08-20)
    STEICO internal technical data sheet (wood fibre for IWI): µ = 5, λD = 0.038 W/(m·K), density 160 kg/m³, bonded over ≥ 80 % of the surface.
  14. Passipedia — Passive House Institute — Thermal protection using interior insulation (2019 · accessed 2026-08-20)
    Passipedia (PHI) uses conductivity classes 035 to 040 for interior insulation, i.e. λ = 0.035–0.040 W/(m·K). The 0.032 of high-performance wools does not appear in this source.
  15. Recticel Insulation (fabricant — donnée produit) — Fiche technique IP PIR 022 (pied de page 211025) (2021-10-25 · accessed 2026-09-04)
    Manufacturer data, sheet footer dated 211025: PIR λD = 0.022 W/(m·K), µ = 50–100; composite panels with laminated mineral wool reach 0.035–0.040 W/(m·K). Hence the 0.022–0.040 range.
  16. Calsitherm Silikatbaustoffe GmbH (fabricant — donnée produit) — CALSITHERM Klimaplatte — Technische Hinweise 2018 (2018 · accessed 2026-08-20)
    Manufacturer data: Calsitherm Klimaplatte λ = 0.062 W/(m·K) (measured 0.059), µ = 3; Multipor λD = 0.042–0.047 W/(m·K), µ = 2–3. The stated range is correct.
  17. Calsitherm Silikatbaustoffe GmbH (fabricant — prescription de mise en œuvre) — CALSITHERM Klimaplatte — Technische Hinweise 2018 (2018 · accessed 2026-08-20)
    Calsitherm: boards must be bonded 'hohlraumfrei und vollflächig' (void-free, full-surface); dab or partial bonding is not system-compliant and causes uncontrolled condensation behind the insulation.
  18. STEICO SE (fabricant — donnée produit) — Fiche technique STEICO internal — isolant support d'enduit intérieur (2021 · accessed 2026-08-20)
    Manufacturer data: STEICO internal (wood fibre for IWI) λD = 0.038 W/(m·K), µ = 5, density 160 kg/m³, bonded over the full surface (≥ 80 % adhesive coverage).
  19. Office cantonal de l'architecture / EPIQR+ — Articles 117-118 LCI — présentation de Francesco Della Casa, architecte cantonal, République et canton de Genève (2024-03-14 · accessed 2026-08-20)
    LCI art. 117: 'Any construction or significant renovation must be designed and built with materials that minimise its carbon footprint'; art. 118 sets the calculation method.
  20. République et canton de Neuchâtel — Service de l'énergie et de l'environnement — Aide à l'application EN-NE102 « Isolation thermique des bâtiments », édition avril 2023 (base SIA 380/1:2016) (2023-04 · accessed 2026-09-04)
    EN-NE102, April 2023 edition (based on SIA 380/1:2016), table 2 p. 9: opaque element against outside air, U ≤ 0.17 W/(m²K) for new build and 0.25 W/(m²K) for conversion.
  21. République et canton de Genève — SILGeneve — Règlement d'application de la loi sur les constructions et les installations diverses (RCI), L 5 05.01, art. 56 (1978-12-27 · accessed 2026-08-20)
    RCI (rsGE L 5 05.01) art. 56: 'The thermal quality of the building envelope must, unless a particular case applies, comply with the SIA 380/1 standard in force.'
  22. République et canton de Genève — SILGeneve — Règlement d'application de la loi sur l'énergie (REn), L 2 30.01, art. 12B (2010-09-01 · accessed 2026-08-20)
    REn (L 2 30.01) art. 12B, HPE renovation, variant a): MoPEC 2014 weighted energy demand limits increased by 70 % and SIA 380/1 heating demand increased by 50 %.
  23. Source to be established — unverified figure
    Unconfirmed claim: the PHI document 'Criteria for the Passive House, EnerPHit and PHI Low Energy Building Standard' could not be opened. To be sourced or removed before publication.
  24. Passipedia — Passive House Institute — Thermal protection using interior insulation (2019 · accessed 2026-08-20)
    Passipedia (PHI): 'flanking insulation along the interior wall (ca. 40 cm)', with ≥ 20 mm at the window reveal and an insulation wedge on the underside of the slab.
  25. République et canton de Genève — SILGeneve — Règlement d'application de la loi sur les constructions et les installations diverses (RCI), L 5 05.01, art. 56A (1978-12-27 · accessed 2026-09-04)
    RCI art. 56A para. 2: reveals to be upgraded from U ≥ 3.0 W/(m²K). Para. 5, protected buildings: let. a, b and d require glazing U ≤ 1.0; let. c, a second external window, is single-glazed.
  26. pro clima Suisse — Éviter les dégâts au bâtiment (2020 · accessed 2026-08-20)
    pro clima (DIN 4108-type test): 0.5 g of water/m² per winter day by diffusion through an sd = 30 m vapour retarder, versus 800 g per metre of a 1 mm gap by convection — a factor of 1600.
  27. AQC — Agence Qualité Construction — Fiche pathologie bâtiment — Les attaques des bois par les agents biologiques (2013 · accessed 2026-09-04)
    AQC sheet 'Attaques des bois par les agents biologiques': decay results from 'le maintien d'une humidité relative supérieure à 20 %' in the timber — the sheet's wording is ambiguous.
  28. République et canton de Genève — SILGeneve — Règlement d'application de la loi sur l'énergie (REn), L 2 30.01, art. 14 (2010-09-01 · accessed 2026-08-20)
    REn art. 14: exceeding an IDC of 125 kWh/m²·an (450 MJ/m²·an) requires an audit and improvement measures within 12 months.
  29. République et canton de Genève — SILGeneve — Règlement d'application de la loi sur l'énergie (REn), L 2 30.01, art. 14 (2010-09-01 · accessed 2026-08-20)
    REn art. 14: significant IDC exceedance at 222 kWh/m²·an (800 MJ) until 31.12.2026, 180 kWh/m²·an (650 MJ) from 2027 to 2030, then 153 kWh/m²·an (550 MJ) from 2031.
  30. ISO — ISO 6946:2017 — Building components and building elements — Thermal resistance and thermal transmittance — Calculation methods (2017-06 · accessed 2026-08-20)
    ISO 6946 calculation (Rsi = 0.13 m²K/W): Tsi = Ti − U·Rsi·(Ti−Te). Wall U = 1.8 at 20/0 °C → 15.3 °C; at 20/−5 °C → 14.2 °C; after IWI U = 0.30 → 19.2 °C.
  31. Source to be established — unverified figure
    Internal NRG positive estimate (June 2026): no public Swiss cost database (CRB, KBOB, SIA Bulletin) covers internal insulation specifically. Order of magnitude, not contractual.

Further reading

All dossiers →

A wall to insulate from the inside?

Moisture diagnosis, hygrothermal simulation of the wall, choice of system and execution details — the pre-works study costs a few days and avoids years of defects. Let's talk about your wall.

Get in touch